INDUSTRIAL DIAGNOSTICS 

ABOUT US

SERVICES

DESIGN SERVICES

CASE STUDIES

SAFETY & TRAINING

WHAT'S NEW

RESOURCES

CONTACT

  CASE STUDY 5  

  Diagnostic Investigation - Referigeration compressor control system persistent automatic shutdown  

A refrigeration compressor system would go into automatic shutdown and recovery periodically. A data logger was attached to the power input to continually monitor the current and voltage through a 36 hour period.
A graph of current and voltage from the logged data plotted indicates a voltage slump during normal work hours
The most severe problems were noted in the mid-afternoon period, which corresponded to the observed shutdown problems.
Zooming in to the 3 to 4 o clock times gives a clear cause and effect of the voltage dropping and the cut-off of the cooling system.
The power lines were logged again over a working day and the two phases were monitored and logged for voltage difference between phases.
the logger was put onto the power lines while further tests were carried out, having determined that the problems were external to the compound, T&TEC were contacted and corrected the fault - root cause is not known.
Incoming voltages are now much improved and do not dip severely. No voltage below 100 volts detected after fault correction.